RE-Y(St)Y-fl-TIMF & RE-Yw(St)Yw-fl-TIMF
INSTRUMENTATION CABLES, EN 50288-7MULTİ-TRIPLE, PVC INSULATED, INDIVIDUAL & COLLECTİVE SCREENED, PVC SHEATHED
These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc... . Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. For application of 105oC heat resistant, RE-Yw(St)Yw-TIMF cables are suitable. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.
Conductor: Plain copper wire, stranded, IEC 60228 Sınıf 2, TS/DIN EN 60228 Sınıf 2
Insulation (Y): PVC compound, 70 oC grade; EN 50290-2-21
Insulation (Yw): PVC compound, 105 oC grade; EN 50290-2-21
Core identification: Black / Blue / Red; with numbered tape under, separator tape of the pair screen, Upon request ; Black / Blue / Red cores numbered 1-1-1, 2-2-2,…, Other core configurations manufactured upon request.
Triple: Three conductors twisted to a triple
TIMF Construction: Polyester tape above the triple, AL-PES tape, over solid tinned copper drain wire, 0,60 mm, Upon request ; Stranded 0,50 mm2 copper drain wire
Lay-up: TIMF laid up in layers of optimum pitch
Separator: Polyester tape
Outer sheath (Yw): PVC compound, 105 oC grade; EN 50290-2-22
Sheath colour: RAL 9005, Black or RAL 5015, Blue
Screen: AL-PES tape over stranded tinned copper drain, wire 0,50 mm2
Outer sheath (Y): PVC compound, 70 oC grade; EN 50290-2-22
Standard: TS/DIN EN 50288-7
Conductor resistance: 0,50mm2 : 36,7 Ω/km, 0,75mm2 : 25,0 Ω/km, 1,0mm2 : 18,5 Ω/km, 1,3mm2 : 14,2 Ω/km, 1,5mm2 : 12,3 Ω/km
Insulation resistance: Min. 100 MΩ.km
Mutual Capacitance: 0,50 mm2 : max. 160 pF/mr, 0,75 mm2 : max. 160 pF/m, 1,0 mm2 : max. 160 pF/m, 1,3 mm2 : max. 170 pF/m, 1,5 mm2 : max. 170 pF/m
L / R (ratio) (max.): 0,50mm2 : 25 µH/Ω, 0,75mm2 : 25 µH/Ω, 1,0mm2 : 25 µH/Ω1,30mm2 : 40 µH/Ω, 1,5mm2 : 40 µH/Ω
Rated voltage: 500V
Test voltage: Urms core-core : 2000 V, Urms core-screen : 2000 V
Temperature range (2Y): operation : - 30 oC ~ + 70 oC, ınstallation : - 5 oC ~ + 50 oC
Temperature range (2X): operation : - 30 oC ~ + 105 oC, ınstallation : - 5 oC ~ + 50 oC
Min. bending radius: 7,5 x D
Flame retardance test: IEC 60332-1 & EN 60332-1